Guangdong Yufeng Industries Co., Ltd.
Guangdong Yufeng Industries Co., Ltd.

Technical Specifications of RTV Antifouling Flashover Coating

Mar 16 , 2023
No.ItemStandard requirementPaint technical specification
1AppearanceUniform color, no obvious mechanical impurities, and flocculentUniform color, no obvious mechanical impurities, and flocculent
2Surface drying time<45(min)15~17(min)
3HydrophobicityHydrophobicityQav(°)≥100°, Qmin(°)≥90°Qav(°)105~107, 95~97°
HC1~HC2HC1
The weakening property of hydrophobicityQav(°)≥90°, Q min(°)≥85°Qav(°)93~94, 87~88°
HC3~HC4HC1~HC2
Recovery properties of hydrophobicityQav(°)≥95°, Q min(°)90°Qav(°)103~104, 97~99°
HC2~HC3HC1
The transfer properties of hydrophobicityQav(°)≥100°, Q min(°)90°Qav(°)113~114, 103~106°
HC 2~HC 3HC1
4Volume resistivityPv(Ω.m)≥1×14power1.63×14power~1.8×14power
5Relative dielectric constantεr≤3.0εr 2.78~2.81
6Dielectric loss tangent valuetgδ(%)≤0.3tgδ(%)0.26~0.27
7Dielectric strengthE(Kv/mm)≥18E(Kv/mm)22.2~22.8
8Resistance to electrical erosionNot lower than TMA4.5TMA4.5
9Adhesion forceCircle method: Better than level 2level 1
10Abrasion resistance≤0.05(g)0.031~0.033(g)
11Chemical resistant agentIn 25.3% acid, alkali, salt reagent for 24h, there should be no shedding, wrinkling, foaming, discolourationNo shedding, wrinkling, foaming, discoloration
Oil resistanceIn 100°C transformer oil for 24h, there should be no shedding, wrinkling, foaming, discolorationNo shedding, wrinkling, foaming, discoloration
12Power frequency wet lightning voltageThe frequency wet lightning voltage of coated insulators shall not be reduced relative to that of uncoated insulatorsU1=51.5~51.6KV
U2=46.7KV
13Anti-fouling lightning voltageU1/U2≥1.5U1/U2 2.01~2.03
14FlammabilitySuperior to the FV-2 stageFV-0
15Solid contentSolid content(%)≥50Solid content(%)54.7~55.0
16Shear strengthT(Mpa)≥3.0T(Mpa)3.06
17Tear strength≥12KN/m17.92~20.12KN/m
18Aging resistanceAfter 1700h salt spray test of coating (1) each series of porcelain bottles does not exceed 3 wen without overcurrent interruption; (2) No trace of electric leakage, electric erosion does not reach the surface of porcelain; (3) hydrophobic migration is HC2 ~ HC3; (4) The bonding tensile shear strength is not less than 3.0Mpa(1) No overcurrent interrupt; (2) No trace of electric leakage, electric erosion does not reach the surface of porcelain; (3) hydrophobicity was HC1; (4) The bonding tensile shear strength is 3.01Mpa, 3.00Mpa, 3.00Mpa, 2.98Mpa, 3.03Mpa, respectively


Related Arresters & Insulators News
Copyright © Guangdong Yufeng Industries Co., Ltd. All Rights Reserved.
+86-19576840556
info@gdyfpower.com
+86-19576840556