No. | Item | Standard requirement | Paint technical specification |
1 | Appearance | Uniform color, no obvious mechanical impurities, and flocculent | Uniform color, no obvious mechanical impurities, and flocculent |
2 | Surface drying time | <45(min) | 15~17(min) |
3 | Hydrophobicity | Hydrophobicity | Qav(°)≥100°, Qmin(°)≥90° | Qav(°)105~107, 95~97° |
HC1~HC2 | HC1 |
The weakening property of hydrophobicity | Qav(°)≥90°, Q min(°)≥85° | Qav(°)93~94, 87~88° |
HC3~HC4 | HC1~HC2 |
Recovery properties of hydrophobicity | Qav(°)≥95°, Q min(°)90° | Qav(°)103~104, 97~99° |
HC2~HC3 | HC1 |
The transfer properties of hydrophobicity | Qav(°)≥100°, Q min(°)90° | Qav(°)113~114, 103~106° |
HC 2~HC 3 | HC1 |
4 | Volume resistivity | Pv(Ω.m)≥1×14power | 1.63×14power~1.8×14power |
5 | Relative dielectric constant | εr≤3.0 | εr 2.78~2.81 |
6 | Dielectric loss tangent value | tgδ(%)≤0.3 | tgδ(%)0.26~0.27 |
7 | Dielectric strength | E(Kv/mm)≥18 | E(Kv/mm)22.2~22.8 |
8 | Resistance to electrical erosion | Not lower than TMA4.5 | TMA4.5 |
9 | Adhesion force | Circle method: Better than level 2 | level 1 |
10 | Abrasion resistance | ≤0.05(g) | 0.031~0.033(g) |
11 | Chemical resistant agent | In 25.3% acid, alkali, salt reagent for 24h, there should be no shedding, wrinkling, foaming, discolouration | No shedding, wrinkling, foaming, discoloration |
Oil resistance | In 100°C transformer oil for 24h, there should be no shedding, wrinkling, foaming, discoloration | No shedding, wrinkling, foaming, discoloration |
12 | Power frequency wet lightning voltage | The frequency wet lightning voltage of coated insulators shall not be reduced relative to that of uncoated insulators | U1=51.5~51.6KV |
U2=46.7KV |
13 | Anti-fouling lightning voltage | U1/U2≥1.5 | U1/U2 2.01~2.03 |
14 | Flammability | Superior to the FV-2 stage | FV-0 |
15 | Solid content | Solid content(%)≥50 | Solid content(%)54.7~55.0 |
16 | Shear strength | T(Mpa)≥3.0 | T(Mpa)3.06 |
17 | Tear strength | ≥12KN/m | 17.92~20.12KN/m |
18 | Aging resistance | After 1700h salt spray test of coating (1) each series of porcelain bottles does not exceed 3 wen without overcurrent interruption; (2) No trace of electric leakage, electric erosion does not reach the surface of porcelain; (3) hydrophobic migration is HC2 ~ HC3; (4) The bonding tensile shear strength is not less than 3.0Mpa | (1) No overcurrent interrupt; (2) No trace of electric leakage, electric erosion does not reach the surface of porcelain; (3) hydrophobicity was HC1; (4) The bonding tensile shear strength is 3.01Mpa, 3.00Mpa, 3.00Mpa, 2.98Mpa, 3.03Mpa, respectively |